LineLumped
LineLumped represents an \(N\)-phase, \(K\)-conductor lumped EMT line over length
\(\Delta x\). Series current \(\mathbf{i}_{12}\) is directed from terminal 1 to
terminal 2.
Block Diagram

Figure 1: LineLumped model
The conductor-to-phase mappings are shown in the equations and omitted from the diagram for clarity.
Model Parameters
Define the phase- and conductor-index sets
Symbol |
Units |
JSON |
Description |
Note |
|---|---|---|---|---|
\(N\) |
[-] |
|
Number of phases |
Required, positive integer |
\(K\) |
[-] |
|
Number of conductors |
Required, positive integer |
\(\mathbf{c}\) |
[-] |
|
Conductor phase-index list |
\(\mathbf{c} \in \mathcal{N}^K\) |
\(\Delta x\) |
[m] |
|
Line segment length |
Required, positive |
Parameter Validation
Model Derived Parameters
Model Ports
Symbol |
Port |
Type |
Units |
Description |
Note |
|---|---|---|---|---|---|
\(\mathbf{v}_1\), \(\mathbf{i}_1\) |
|
Terminal |
[V], [A] |
Terminal 1 bus voltage and current injection |
\(\mathbf{v}_1, \mathbf{i}_1 \in \mathbb{R}^N\) |
\(\mathbf{v}_2\), \(\mathbf{i}_2\) |
|
Terminal |
[V], [A] |
Terminal 2 bus voltage and current injection |
\(\mathbf{v}_2, \mathbf{i}_2 \in \mathbb{R}^N\) |
Submodels
Symbol |
Description |
Type |
Order |
JSON |
Inputs |
Outputs |
|---|---|---|---|---|---|---|
\(\mathbf{z}\) |
Per-unit-length series impedance |
\(KQ_{\mathbf{z}}\) |
|
\(\mathbb{R}^K\) |
\(\mathbb{R}^K\) |
|
\(\mathbf{y}_1\) |
Per-unit-length shunt admittance at terminal 1 |
\(KQ_{\mathbf{y}}\) |
|
\(\mathbb{R}^K\) |
\(\mathbb{R}^K\) |
|
\(\mathbf{y}_2\) |
Per-unit-length shunt admittance at terminal 2 |
\(KQ_{\mathbf{y}}\) |
|
\(\mathbb{R}^K\) |
\(\mathbb{R}^K\) |
Yp provides one coefficient set; the two terminal instances maintain
independent states. A line without Yp has no shunt admittances.
Submodel Validation
Each submodel is \(K\) by \(K\).
Submodel Wiring
\(\mathbf{y}_1\) and \(\mathbf{y}_2\) read the conductor voltages at their terminals and add their shunt currents to the bus current balances.
Model Variables
Internal Variables
Differential
Symbol |
Units |
Description |
Note |
|---|---|---|---|
\(\mathbf{i}_{12}\) |
[A] |
Series current from terminal 1 to terminal 2 |
\(\mathbf{i}_{12} \in \mathbb{R}^K\) |
Algebraic
None.
External Variables
Differential
Symbol |
Units |
Description |
Note |
|---|---|---|---|
\(\mathbf{v}_1\) |
[V] |
Terminal 1 voltage owned by EMT bus |
\(\mathbf{v}_1 \in \mathbb{R}^N\) |
\(\mathbf{v}_2\) |
[V] |
Terminal 2 voltage owned by EMT bus |
\(\mathbf{v}_2 \in \mathbb{R}^N\) |
Algebraic
None.
Model Equations
Internal Equations
Differential
Algebraic
None.
External Equations
Each shunt carries half of the line admittance.
Initialization
None.
Monitors
Monitor |
Units |
Description |
Note |
|---|---|---|---|
|
[A] |
Series current from terminal 1 to terminal 2 |
\(\mathbf{i}_{12} \in \mathbb{R}^K\) |
|
[A] |
Shunt current of each conductor at terminal 1 |
Output of \(\mathbf{y}_1\), with |
|
[A] |
Shunt current of each conductor at terminal 2 |
Output of \(\mathbf{y}_2\), with |